Ventilation unit compact. Ventilation units KOMPAKT REGO. Overall dimensions of air handling units Compact

Air handling units Compact designed to work in small spaces: apartments, shops, offices, workshops, etc. In a compact sound and heat insulated housing (insulation thickness 25 mm) there are: a filter, a fan, a heater. All fans are equipped asynchronous motor with an external rotor and sealed bearings, which increases their service life. Available in three sizes air handling units with various versions in terms of fan performance and heater power. All units are equipped with EU3 class filters. To indicate the degree of filter contamination, a pressure sensor is included with each unit. Units with electric heater can be mounted in any position. Units with a water heater must be mounted in a position that ensures normal ventilation of the heat exchanger. They are easily connected to rectangular ducts. Small size Air handling units Compact allow you to install them depending on the size in suspended ceilings depth of at least 350-400 mm. During installation, it is necessary to provide access for servicing the equipment and replacing the filter. For work management air handling units SCM and MSS control modules have been developed. They consist of an RCU-30 control panel and an automation board. The fan speed control of the Compact-1 and Compact-2 units is carried out by a three-stage transformer, Compact-3 by a frequency converter. To control the temperature of the supply air at the outlet of the unit, depending on the power of the electric heater, a triac temperature controller Pulser or TTC is provided, and for the water heater OPTIGO. The engines of the Compact-1 and Compact-2 units are protected by built-in thermal contacts with automatic restart. Motors of Compact-3 installations do not have thermal contacts; their current protection is provided in the automation board. The electrical heaters of the units are equipped with a two-stage overheating protection. The first stage is set to 55°C and restarts automatically, the second stage is set to 120°C and restarts manually. To protect the water heater from defrosting, a capillary thermostat for protecting the heat exchanger is provided. minimum temperature air flow. Additionally, it is necessary to install a temperature sensor to protect the heat exchanger at the return water temperature. IN additional equipment includes: quick couplers, speed controllers, temperature controllers, check valve, muffler, air distribution and protective grilles, etc.

Technical characteristics of air handling units Compact

Air handling units Compact

Air consumption, m³/h

Voltage, V/f

Heater power, kW

Fan power, kW

Weight, kg

Compact 1109M

Compact 1112M

Compact 1115M

Compact 11B2M

Compact 11B4M

Compact 2112M

Compact 2117M

Compact 2127M

Compact 21B2M

Compact 21B4M

Compact 3124

Compact 3132

Compact 3145

Compact 31B2

Compact 31B3

Compact 31B4

* The power of the water heater is given for air temperature -26°С, water 95/70°С

Overall dimensions of air handling units Compact

type of instalation

d**, mm

Compact 1109M

Compact 1112M

Compact 1115M

Compact 11B2M

Compact 11B4M

Compact 2112M

Compact 2117M

Compact 2127M

Compact 21B2M

Compact 21B4M

500

Our company carries out professional installation of ventilation systems of any level of complexity.
The main advantages of cooperation with us:
installation of turnkey ventilation;
installation of ventilation systems of any type at facilities for various purposes;
use of modern innovative energy-saving technologies;
direct cooperation with the largest manufacturers of climate equipment;
providing a full package of documents;
low prices.
We perform:
installation of exhaust ventilation;
installation supply ventilation;
installation supply and exhaust ventilation;
including installation of installations with natural and mechanical impulses;
complex development of engineering systems, including ventilation, air conditioning and heating.

Schedule

All installation work performed on weekdays. If there is an urgent need, in agreement with the customer, work can be carried out on weekends.

ClimatSeason is an official dealer of the largest manufacturers of climate control equipment, including most of the well-known Japanese, Korean, Russian and European brands.
The official guarantee is presented:
for the supplied equipment (set by each manufacturer individually and ranges from 1 to 3 years);
for installation (1 year).
Warranty conditions:
correct installation and operating conditions of equipment;
integrity of the case and seals;
observance of terms and frequency of service maintenance;
preservation of purchase documents (filled out warranty card, cashier's check when paying in cash or invoice for non-cash transfer of funds)
The procedure for eliminating deficiencies during the warranty period of the equipment:
notification of the seller about the identified shortcomings no later than 5 days from the moment they were discovered (the letter is sent by e-mail or regular mail to the address: 125040, Moscow, Verkhnyaya st., 34, p. 11 or by e-mail);
departure of a specialist to the object within 5 days from the date of receipt of the message.
Please check the warranty card when purchasing and keep it for the entire warranty period. Before buying, we recommend that you carefully read the terms of warranty service and the rules for operating the equipment.

Air handling units in a frame-panel housing COMPACT from a Russian manufacturer of ventilation equipment ARCTOS Designed for use in residential and public buildings. Ventilation units capacity up to 1050 m3/h COMPACT-1 1115M complete with electric heater, filter, damper and fan. The unit is standardly equipped with filters of cleaning class G3, a pressure sensor is provided to control the degree of contamination of the filter.

Advantages of air handling units COMPACT:

  • Six standard sizes of ventilation units with a maximum capacity of up to 7000 m3/h.
  • Ventilation units have a monoblock, suspended design.
  • Are completed with an electroheater or the 2nd, 3rd, or 4th row water heat exchanger.
  • The package includes a filter with a degree of purification G3. Complete set with filters of higher purification is made on a separate request.
  • The body is made from aluminum profile and connecting elements. Steel sandwich panels filled with non-hot heat and sound insulating material 25 mm thick.
  • Standard SCM…N control module (RCU-30 control panel and automation panel), which controls the operation of the air handling unit.
  • it is possible to adjust the fan speed with the help of an additional device - a 3-stage transformer.
  • supply air temperature control at the outlet of the unit is carried out using a triac temperature controller Pulser or TTC (electric heater), for the Aqua water heater.
  • built-in motor protection with automatic restart.
  • Air handling units with an electric air heater are equipped with a 2-stage overheating protection.
  • Units with a water heater are equipped with a capillary thermostat to protect the heater from freezing at low air temperatures. Additionally, a temperature sensor (on the return water pipe) must be provided to protect the heat exchanger.
  • The dimensions of the air handling units allow them to be installed in suspended ceilings up to 400 mm deep.
  • Large selection of accessories for connection, installation and control of the air handling unit.
  • The units are delivered assembled and ready for connection.

The advantage of air handling units with an electric heater (heater) is, first of all, simple installation, as well as the absence of problems associated with the possibility of defrosting the water heater. The electric heater provides fast warming up of supply air to the required temperature. Air handling units COMPACT have specially designed control devices SCM, which controls the operation of all elements (damper, heater, fan), and performs protective functions - it protects the fan motor from short circuit and overheating. In addition, the SCM control device monitors the degree of contamination of the filter.

Frame-panel air handling units from ARCTOS- ease of installation the lineup and high performance. The body of the unit, consisting of "sandwich" panels, performs a heat-insulating and sound-insulating function, preventing the spread of noise from the installation site of the equipment to the manned room.

The goods are delivered on a prepaid basis.

Ventilation units "Compact 1" and "Compact 2" are designed to work in small spaces: apartments, shops, offices, workshops, etc.
In a compact sound and heat insulated housing (insulation thickness 25 mm) are placed: filter, fan, heater. The fans of the "Compact 1" and "Compact 2" units are equipped with an asynchronous motor with an external rotor. All units are equipped with EU3 class filters. To indicate the degree of filter contamination, a pressure sensor is included with each unit.

Installation
Units with electric heater can be mounted in any position. Units with a water heater must be mounted in a position that ensures normal ventilation of the heat exchanger. They are easily connected to rectangular ducts. The small dimensions of the units allow them to be installed in false ceilings and shallow wall niches. During installation, it is necessary to provide access for servicing the equipment and replacing the filter.

Speed ​​and temperature control
Control modules SCM and MSS have been developed to control the operation of air handling units. They consist of an RCU-30 control panel and an automation board.
The fan speed of the "Compact 1" and "Compact 2" units is controlled by a three-stage transformer. To control the temperature of the supply air at the outlet of the unit, depending on the power of the electric heater, a triac temperature controller Pulser or TTC is provided, and for the water heater OPTIGO.

Motor and heater protection
The engines of the "Compact 1" and "Compact 2" units are protected by built-in thermal contacts with automatic restart. The electrical heaters of the units are equipped with a two-stage overheating protection. The first stage is set to 55°C and restarts automatically, the second stage is set to 120°C and restarts manually. To protect the water heater from defrosting, a capillary thermostat is provided to protect the heat exchanger by the minimum temperature of the air flow. Additionally, it is necessary to install a temperature sensor to protect the heat exchanger from the return water temperature.

Accessories
Air valves, silencers, air distribution and protective grilles, etc.

Dimensions

Compact 1109M

A 320
B
Cmm1070
D
E
Noise characteristics

Compact 1109M

LwA tot (total noise level)LwA (noise level in the octave range)
31,5 63 125 250 500 1000 2000 4000 8000
To the entrance55 62 59 59 56 65 59 53 53 51 45
To the exit63 70 52 64 62 68 65 65 64 61 55
To the environment46 53 56 57 55 54 47 43 46 46 41

Operating characteristics

Installation
¤ All units are supplied fully assembled and ready to connect.
¤ Electrical connection and installation must only be carried out by qualified personnel in accordance with the installation instructions.
¤ The electrical parameters must comply with the specifications on the installation plate.
¤ All wiring and connections must be made in accordance with safety regulations.
¤ The electrical connection must be made in accordance with the wiring diagram according to the markings on the terminals.
¤ The units must be earthed.
¤ The units must be installed according to the airflow direction.
¤ The units must be mounted in such a way that there is access for safe maintenance.

Working conditions
¤ The units must not be operated in explosive areas.
¤ The units must not be used to transport explosive gases, dust, soot, flour, etc.
¤ The units are designed for continuous operation. It is not recommended to turn the equipment on and off frequently.
¤ Noise related problems can be eliminated by using a silencer (one of the supplied accessories).

Service
The only maintenance required is cleaning. It is recommended to inspect and clean the filter every month, the fan every six months of continuous operation to prevent imbalance or premature failure of the fan.
Before servicing, make sure
¤ Power supply interrupted.
¤ The fan impeller has come to a complete stop.
¤ Heater, motor and fan impeller have completely cooled down.
When cleaning the installation
¤ Do not use aggressive detergents, sharp objects and devices operating under high pressure.
¤ Ensure that the fan impeller is not out of balance or misaligned.
¤ If the fan noise is abnormally high, check the impeller for misalignment.
¤ Bearings, if damaged, must be replaced.

In the event of a malfunction
¤ Check that the system is receiving voltage.
¤ Turn off the power and make sure that the fan blades are not blocked and the current protection has not tripped.
¤ Check capacitor connection. If after checking the unit does not turn on or the fan or heater protection trips, contact your supplier.
¤ In case of return of the unit - clean the filter, heater, blades and fan motor; connecting wires must not be damaged; a written description of the malfunction is required - a statement.

Up